GLOWORM 30 CI *F22 *
2 posters
Page 1 of 1
GLOWORM 30 CI *F22 *
*has heating no hot water*
symptoms are simlar to a scaled plate heat exchanger
when in demand for hot water boiler fires , then turns off,
displays f22 ==manufactures say replace pressure switch.
actual fault was insufficiant gas supply at boiler.
standing pressure = 20 mbar
working pressure = 8 mbar
checked gas meter (under a pile of stinking shoes) and ecv was 3/4 closed .
symptoms are simlar to a scaled plate heat exchanger
when in demand for hot water boiler fires , then turns off,
displays f22 ==manufactures say replace pressure switch.
actual fault was insufficiant gas supply at boiler.
standing pressure = 20 mbar
working pressure = 8 mbar
checked gas meter (under a pile of stinking shoes) and ecv was 3/4 closed .
tommy nash- Posts : 6
Join date : 2010-02-12
Re: GLOWORM 30 CI *F22 *
Good one that Tom. Just shows the benefit of checking inlet working pressures and preliminary electrical checks on every job!! Wouldn't help with the shoes though.