GLOWORM 30 CI *F22 *

2 posters

Go down

GLOWORM 30 CI *F22 * Empty GLOWORM 30 CI *F22 *

Post  tommy nash Mon Feb 22, 2010 11:25 am

*has heating no hot water*

symptoms are simlar to a scaled plate heat exchanger

when in demand for hot water boiler fires , then turns off,
displays f22 ==manufactures say replace pressure switch.

actual fault was insufficiant gas supply at boiler.

standing pressure = 20 mbar
working pressure = 8 mbar

checked gas meter (under a pile of stinking shoes) and ecv was 3/4 closed .
tommy nash
tommy nash

Posts : 6
Join date : 2010-02-12

Back to top Go down

GLOWORM 30 CI *F22 * Empty Re: GLOWORM 30 CI *F22 *

Post  Rich S Mon Feb 22, 2010 3:18 pm

Good one that Tom. Just shows the benefit of checking inlet working pressures and preliminary electrical checks on every job!! Wouldn't help with the shoes though.